Refrigerator Electrical Test Procedures

Supply and control switch

1. Check the electrical supply at the power point, the fuse and the fuse rating.
2. Ensure that the control switch is set to the on position, and check the
electrical supply to the control. If there is supply to the input side of the control, bridge out the control contacts with a jumper wire or join the two control wires together; this will effectively take the control out of circuit ( Figure 45 )
3. If the compressor fails to start, check the supply voltage at the compressor terminals or at the relay terminal board.

refrigerator-input-test-circuit

Overload protector

If the compressor is cold to the touch it is evident that it has been idle for some time. The overload protector should be checked for continuity or by bridging the two contacts as described for the control switch (Figure 46). Try to start the unit.

Windings

Isolate the unit electrically and remove the electrical leads from the compressor terminals, or the relay if it is a push-on type.

refrigerator-overload-protector-test

refrigerator-compressor-winding-test

Check the compressor windings for continuity and resistance values (Figure 47). The highest resistance value between any two terminals is the sum of two winding resistances (start and run terminals). The next highest resistance value between two terminals is the value of the start winding (start and common terminals). The lowest resistance value is that of the run winding (run and common terminals).

Test cord

If the check shows that the continuity and resistances are satisfactory, connect a test cord (see Figure 48). With the test cord connected, switch on the power supply. At this stage the compressor will be trying to start on the run winding only and a humming sound should be audible.

refrigerator-test-cord-arrangement

Depress the test cord bias switch to bring the start winding in circuit, and hold for 2-3 seconds. The compressor should start. If the compressor starts when the start winding is in circuit but stops when the bias switch is released, the run winding is defective. Failure to start at all means that the start winding is defective. In either case a replacement compressor will be required.

A maximum deflection recorded on the ohmmeter indicates that the compressor motor is down to earth, and will probably blow fuses when the windings are energized.

When capacitors are included in the circuit they should be connected in series if a test cord is used; Figure 48 shows a start capacitor in series with the start winding.

The larger hermetic and semi-hermetic 220/240 volt a.c. 50 hertz capacitorstart/ capacitor-run motor compressors draw considerable starting currents and it is advisable to use a heavy duty test cord similar to the type shown in Figure 49 when testing a compressor operation. The connection procedure is as follows:

refrigerator-heavy-duty-test-cord

1. With all switches in the ‘off’ position, attach the Three motor leads of the test cord to the compressor terminals.
2. Attach a known good capacitor of the correct microfarad rating to the start capacitor leads of the test cord. (If two start capacitors are fitted, connect them in parallel.)
3. Attach the appropriate capacitor to the ‘run capacitor’ leads of the test cord.
4. Move the ‘run capacitor’ switch to the ‘on’ position.
5. Ensure that the earth lead of the test cord locates to the compressor screw and makes good contact.
6. Connect the test cord to the mains supply.
7. Hold the start switch at the ‘on’ position and move the main switch to the ‘on’ position.
8. Release the start switch when the motor is up to speed.
If the compressor fails to operate it must be replaced. If the compressor runs on the test cord, then the fault may be in the overload protector or starting relay.

Capacitors

If the unit fails to start with the test cord it could also mean that the capacitor is unserviceable. It should be tested with a capacitor tester if available.

Another means of testing a capacitor is to connect it across a 50 Hz supply in series with an ammeter and several lamps to provide a resistive load. The voltmeter should be connected across the capacitor terminals as shown in Figure 50.

Capacitance in microfarads (uF) is given by (amperes/volts)x 3200. For example, suppose a capacitor rating is 80-105. If the mains supply is 240 V 50 Hz and the current drawn is 7.5 A, then (7.5/240) x 3200 = 100 uF. This
shows that the capacitor is functioning within the design rating. It must be emphasized that this method must not be used to select a capacitor.

refrigerator-capacitor-testing

Should a capacitor show any signs of leakage or damage to the outer casing, it should be changed.

Potential relay

First ensure that no capacitor in the circuit is defective or shows signs of leakage or damage.

1. Check for continuity by removing the relay and measuring the resistance across the relay coil (see Figure 51). In this case the reading is taken between terminals 2 and 5, but this may differ according to the relay type. A high resistance should be recorded. If a zero reading is recorded then the coil is open circuit.
2. Replace the relay and switch on the unit. If the contacts are stuck open, a humming sound should be heard; the compressor is trying to start on the run winding only. After 15-20 seconds the motor will trip out on the overload.
3. Isolate the unit and install a jumper wire across the switch terminals, in this case between terminals 1 and 2. Switch on the unit. The jumper wire should include a bias switch for safety.
4. Hold the bias switch in circuit for approximately 5 seconds to allow the compressor to reach its design speed. Then release the bias switch; the compressor should continue to run. This means that the relay contacts are stuck open.

This test will only be effective if the capacitors are serviceable, and is similar to using a test cord.

refrigerator-potential-relay-testing

One Reply to “Refrigerator Electrical Test Procedures”

Leave a Reply

Your email address will not be published. Required fields are marked *