Refrigerator Troubleshooting Diagram

Restricted Capillary Tube

without comments

The capillary tube is restricted when the flow of liquid refrigerant through the tube is completely or partially interrupted. Symptoms are similar to those of a system that has lost its refrigerant. However, the major part of the refrigerant charge will be pumped into the high side (condenser), the same as with a moisture restriction. The suction pressure will range slightly below normal to very low (2 to 20 in. vacuum), depending on the amount of restriction.